FT-0100 Water and Visual Clarity Test for Diesel Fuel

Description

This is a simple two-part test in which diesel, biodiesel, jet fuel or heating oil is tested for

  • Visual clarity
  • Presence of entrained (dissolved) water

Visual clarity testing will often reveal particulates such as sediment, glycerin, or microbial residue. In the second part of the test, a vial of water detection fluid is added to the fuel, allowing the detection of entrained water to as low as 200ppm. At 500ppm, the detection fluid leaves a distinct red ring at the bottom of the sample bottle.

When to use it

This test should be used as an initial screening test for fuel deliveries and for periodic monitoring of fuel quality at the dispenser and storage tanks. It can also be used as a vehicle maintenance diagnostic to detect entrained water (a major cause of blown injector tips). Works for diesel fuels, biodiesel, and biodiesel blends.

Approximate time to perform test(s)

One minute for each of part of the two part test. Results in 5 minutes.